Escaping tunnels safely

In the Netherlands, tunnels 500 metres or longer must be fitted with a ventilation system (see Building Decree 2012, Article 3.32, paragraph 7).
The purpose of this ventilation system is to extract exhaust gases and, in the event of a fire, ventilate the tunnel in such a way that backlayering does not occur. Backlayering means that smoke flows back against the direction of ventilation.
If backlayering does not occur, so that smoke flows downstream, people can escape upstream and emergency services can approach the fire with the wind at their backs. However, this type of ventilation may not be sufficient to provide a safe escape route for everyone in the tunnel. Tunnels are therefore also equipped with escape routes leading to a safe area.
Most tunnels in the Netherlands have an escape passage running parallel to the tunnel tube or tubes. Given its height, the passage is usually divided vertically by installing a grating floor. The upper part of the escape passage is used as a plant room. These two functions, escape route and plant room, can coexist perfectly well.

Creating positive pressure
In the event of a fire in a tunnel, smoke can enter the escape passage through open doors. This can be prevented by pressurising the escape passage. The positive pressure prevents smoke from entering through gaps around closed doors. When one or more doors are open, the pressurisation system creates a positive airflow from the pressurised space/escape passage into the incident tunnel tube. This prevents smoke from entering the escape passage.
Airflows must not be too strong
The design must therefore take account of the size of the doors and the maximum number that can be open at the same time, so that even in the worst-case scenario, air still flows from the pressurised space into the incident tunnel tube. However, this airflow must not be too strong. If it is, people may be unable to open the door or escape against the airflow. Airflow is therefore limited to 6 m/s across an open doorway or 2.5 m/s across the tunnel tube cross-section, measured 1.8 metres above walkway level. This establishes all the design parameters.

Providing redundancy
An escape passage is pressurised by using fans to blow the required volume of air into it. This is relatively straightforward. Excessive air speeds can be avoided by installing pressure relief dampers, which discharge surplus air directly outside. Alternatively, a variable-speed drive can be used to increase or reduce fan speed in response to measured pressure differences. As the system moves outside air, the fans do not need to meet any additional requirements, such as resistance to higher temperatures. However, it is advisable to provide redundancy. If one fan fails, the standby fan is brought into operation immediately and can deliver the required airflow. Supply fans are usually installed at the end of the escape passage. However, this means that if smoke exits into the incident tunnel tube at one end, it may be drawn in by the pressurisation system's supply fans. For this reason, a second, equally redundant air supply is often installed at the other end, with one side activated depending on the location of the fire.
In addition to tunnel tubes, cross-passages can also be fitted with a pressurisation system or with a ventilation system that creates a positive airflow from the passage into the incident tunnel tube.